title: Troubleshooting - Device Connectivity Status
slug: bhdo/troubleshooting-device-connectivity-status
createdAt: 2022-06-06T16:56:49.000Z
---

At times, a device may display as **Disconnected**.

The following table explains conditions that might cause a device to disconnect, the reasons it disconnected, and the steps to connect the device:

| **For this condition**                                                                                                                                                                                                                                                                                                                                                                                                | **To connect the device**                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         |
| --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- | ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Free Tag: Explicit register name required**<br />****<br />Certain device drivers do not have a list of register names in the DeviceHub Add Tag form.<br /><br />When a list of registers is not provided, the case-sensitive register name must be entered exactly as it is defined in the PLC.<br /><br />The device does not display a **Connected** status until a tag with a correct register name is created. | Add a tag with a case sensitive register name. See [Add Tags](https://public-docs.litmus.io/bhdo/add-tags) to learn more. <br /><br /><br />                                                                                                                                                                                                                                                                                                                                                                                                      |
| **HID Device in Wait State**<br />Some HID (Human Interface Devices), such as barcode scanners, are always disconnected and only show a connected status when they send data to Belden Horizon Data Operations.                                                                                                                                                                                                       | This is a temporary state and no intervention is required. The device connects when there is data to receive.                                                                                                                                                                                                                                                                                                                                                                                                                                     |
| **Incorrect PLC Configuration**<br /><br />If configuration changes have been made to a PLC, the best way to ensure accurate status is to delete and recreate the device in DeviceHub.                                                                                                                                                                                                                                | 1. Delete the device. See [Manage Devices](https://public-docs.litmus.io/bhdo/manage-devices#manage-individual-devices) for more information.<br />2. Create a new device with the correct PLC configuration. See [Connect a Device](https://public-docs.litmus.io/bhdo/connect-a-device) for more information.                                                                                                                                                                                                                                   |
| **Incorrect Tag Information**<br /><br />To prevent the PLC from going into fail-safe mode or from crashing the process when a tag has incorrect information, Belden Horizon Data Operations disconnects communication with the PLC.<br /><br />For example, a tag may contain an incorrect address.                                                                                                                  | 1. Monitor all the tags in flows to identify the bad tag.<br />2. Find the tag with a success flag set to *false*.<br />3. Delete the tag from DeviceHub. See [Manage Tags](https://public-docs.litmus.io/bhdo/manage-tags#manage-existing-tags) for more information.<br />4. If there is no data on the flows, restart the PLC. If a node in a flow indicates "waiting for messages" and nothing is displayed in the debug console, this means that Belden Horizon Data Operations has stopped communicating with the PLC, so there is no data. |